Tableau avec les données techniques pour FVQ-C / RZQSG-LV1/LY1

FVQ71CVEB / RZQSG71L2V1B FVQ100CVEB / RZQSG100L7V1B FVQ100CVEB / RZQSG100L7Y1B9 FVQ125CVEB / RZQSG125L7V1B FVQ125CVEB / RZQSG125L7Y1B9
Poff (mode arrêt) W 0.0 0.0 0.0 0.0 0.0
Rafraîchissement Psb (mode veille rafraîchissement) W 7.0 7.0 7.0 7.0 7.0
  Cooling-=-Cooling cdc degradation cooling 0.25 0.25 0.25 0.25 0.25
Efficacité saisonnière (selon la norme EN14825) Rafraîchissement Pdesign kW 6.80 9.50 9.50 12.00 12.00
    Consommation énergétique annuelle kWh 466 650.685 650.685 975 975
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 5.11 5.11 5.11 4.31 4.31
    Condition D (20 ℃ - 27/19) Pdc kW 3.64 4.03 4.03 3.96 3.96
      puissance absorbée kW 0.42 0.51 0.50 0.50 0.50
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 8.73 7.97 8.14 7.88 7.88
    Condition C (25 ℃ - 27/19) puissance absorbée kW 0.54 0.75 0.74 1.01 1.02
      Pdc kW 3.52 4.60 4.60 5.69 5.69
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 6.49 6.13 6.22 5.61 5.59
    Condition A (35 °C - 27/19) puissance absorbée kW 2.12 2.96 2.96 4.15 4.15
      Pdc kW 6.80 9.50 9.50 12.00 12.00
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.21 3.21 3.21 2.89 2.89
    Condition B (30 ℃ - 27/19) Pdc kW 5.01 7.00 7.00 8.84 8.84
      puissance absorbée kW 1.30 1.55 1.61 3.36 3.34
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 3.85 4.50 4.34 2.63 2.65
  Chauffage (climat tempéré) Consommation énergétique annuelle kWh 2,327 2,799 2,799 2,791 2,791
    Pdesign kW 6.33 7.60 7.60 7.60 7.60
    Puiss. calor. secours nécess. sous conditions conception kW 0.60 0.57 0.54 0.37 0.37
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scop a A A A A A
    TBivalente Pdh (puiss. calor. déclarée) kW 5.60 6.72 6.72 6.72 6.72
      Puissance absorbée kW   2.19 2.20 2.27 2.28
      Tbiv (température bivalente) °C -7 -7 -7 -7 -7
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 2.16 3.06 3.05 2.96 2.95
    Condition C (7 ℃) Pdh (puiss. calor. déclarée) kW 2.88 3.02 3.01 3.18 3.18
      Puissance absorbée kW   0.58 0.57 0.59 0.60
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 6.06 5.22 5.25 5.36 5.35
    TOL Tol (limite temp. de fonctionnement) °C -15 -15 -15 -15 -15
      Pdh (puiss. calorifique déclarée) kW 5.96 7.54 7.64 8.07 8.07
      Puissance absorbée kW 3.46 3.72 3.85 3.76 3.75
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 1.72 2.03 1.99 2.15 2.15
    Condition A (-7 °C) Pdh (puis. calor. déclarée) kW 5.60 6.72 6.72 6.72 6.72
      Puissance absorbée kW   2.19 2.20 2.27 2.28
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 2.16 3.06 3.05 2.96 2.95
    Condition D (12 ℃) Pdh (puiss. calor. déclarée) kW 3.27 3.45 3.44 3.64 3.64
      Puissance absorbée kW   0.56 0.56 0.57 0.58
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 6.90 6.13 6.17 6.35 6.33
    Condition B (2 ℃) Puissance absorbée kW   1.37 1.38 1.40 1.40
      Pdh (puiss. calor. déclarée) kW 4.07 4.96 4.95 5.13 5.13
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 3.83 3.61 3.60 3.66 3.67
Puissance frigorifique Nom. kW 6.8 9.5 9.5 12.0 12.0
Pck (mode résistance de carter) W 0.0 0.0 0.0 0.0 0.0
Efficacité nominale Annual energy consumption kWh 1,059 (0.000) 1,480 (0.000) 1,480 (0.000) 2,135 (0.000) 2,135 (0.000)
  Directive sur l'étiquetage énergétique Chauffage A A A C C
  Nominal efficiency-=-Cop 3.21 3.21 3.21 2.81 2.81
Chauffage Psb (mode veille chauffage) W   14.0 14.0 14.0 14.0
  Heating-=-Heating cdh degradation heating 0.25 0.25 0.25 0.25 0.25
Puissance calorifique Nom. kW 7.5 10.8 10.8 13.5 13.5
Pto (Thermostat off) W 60.0 135.0 135.0 135.0 135.0
Saison froide incluse Oui Oui Oui Oui Oui
Remarques Valeurs EER/COP conformes à la norme Eurovent 2012, pour utilisation hors UE uniquement Valeurs EER/COP conformes à la norme Eurovent 2012, pour utilisation hors UE uniquement Valeurs EER/COP conformes à la norme Eurovent 2012, pour utilisation hors UE uniquement Valeurs EER/COP conformes à la norme Eurovent 2012, pour utilisation hors UE uniquement Valeurs EER/COP conformes à la norme Eurovent 2012, pour utilisation hors UE uniquement
  Efficacité nominale : rafraîchissement à charge nominale 35°/27°, chauffage à charge nominale 7°/20° Efficacité nominale : rafraîchissement à charge nominale 35°/27°, chauffage à charge nominale 7°/20° Efficacité nominale : rafraîchissement à charge nominale 35°/27°, chauffage à charge nominale 7°/20° Efficacité nominale : rafraîchissement à charge nominale 35°/27°, chauffage à charge nominale 7°/20° Efficacité nominale : rafraîchissement à charge nominale 35°/27°, chauffage à charge nominale 7°/20°